Replies: 2 comments
-
Hi @ltwcare |
Beta Was this translation helpful? Give feedback.
0 replies
-
@ltwcare Did you get an answer ? |
Beta Was this translation helpful? Give feedback.
0 replies
Sign up for free
to join this conversation on GitHub.
Already have an account?
Sign in to comment
Uh oh!
There was an error while loading. Please reload this page.
-
I am using version 1.3 of python-snap7 to read data from an S7-300 PLC. Reading out the data works perfectly, both on inputs, flags and data blocks. However, as soon as I execute the function 'get_cpu_info()', the PLC crashes and all LEDs starts to flash. To bring the PLC 'back to life', it must be completely powered down.
Python version: 3.10.6
Python Snap7: v1.3
Reproducible on the following PLCs
Message buffer PLC after restart
Number | Time | Date | Event
1 | 12:46:10:971 pm | 20.09.2023 | Mode transition from STARTUP to RUN
2 | 12:46:10:967 pm | 20.09.2023 | Request for manual warm restart
3 | 12:46:10:763 pm | 20.09.2023 | Mode transition from STOP to STARTUP
4 | 12:45:58:008 pm | 20.09.2023 | Memory reset executed
5 | 12:45:50:993 pm | 20.09.2023 | STOP caused by CPU memory management
6 | 12:45:50:993 pm | 20.09.2023 | Power on backed up
7 | 12:45:50:993 pm | 20.09.2023 | Illegal module: replace module and reset memory
8 | 12:42:29:983 pm | 20.09.2023 | DEFECTIVE: internal system error
9 | 11:45:21:496 am | 20.09.2023 | Mode transition from STARTUP to RUN
10 | 11:45:21:492 am | 20.09.2023 | Request for manual warm restart